(Giá chưa bao gồm VAT)
6ES7231-4HF32-0XB0
SIMATIC
S7-1200, Analog input, SM 1231, 8 AI, +/-10 V, +/-5 V, +/-2.5 V, or 0-20 mA/4-20 mA, 12 bit+sign or (13 bit ADC)
General information
Product type designation SM 1231, AI 8×13 bit
Supply voltage
Rated value (DC) 24 V
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 90 mA
Power loss
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 8; Current or voltage differential inputs
permissible input voltage for voltage input (destruction limit), max. 35 V
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. 625 µs
Input ranges
● Voltage Yes; ±10V, ±5V, ±2.5V
● Current Yes; 4 to 20 mA, 0 to 20 mA
● Thermocouple No
● Resistance thermometer No
● Resistance Yes
Input ranges (rated values), voltages
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) ≥9 MOhm
● -2.5 V to +2.5 V Yes
— Input resistance (-2.5 V to +2.5 V) ≥9 MOhm
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) ≥9 MOhm
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 280 Ω
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 280 Ω
Thermocouple (TC)
Temperature compensation
— parameterizable No
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit; + sign
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 V for interference frequency 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Errors/accuracies
Temperature error (relative to input range), (+/-) 25 °C ±0.1%, to 55 °C ±0.2% total measurement range
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes
Diagnostics indication LED
● for status of the inputs Yes
● for maintenance Yes
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 180 g
last modified: 06/04/2020
Đánh giá
Chưa có đánh giá nào.